The 5600 Series mechanical heat detectors offer a full line of configurations to accommodate a broad range of applications. Both single- and dual-circuit models are offered, each available for low- and high-temperature ratings with either fixed temperature or combination fixed-temperature/rate-of-rise (ROR) activation. The 5600 Series models include the 5601P, 5602, 5603, 5604, 5621, 5622, 5623 and 5624.
Overview
- Multiple configurations available:
- Fixed-temperature (non-resettable) or combination fixed (non-resettable)/rate-of-rise (self-restoring)
- Low-temperature and high-temperature ratings
- Single-circuit and dual-circuit
- Easy-to-read alphanumeric identification of detector type and temperature rating
- External collector provides visual indication of activation
- Reversible mounting bracket for flush- and surface-mount installations
Specifications
Physical/Operating Specifications
- Maximum Installation Temperature 5601P, 5603, 5621, and 5623: 100°F (38°C)5602, 5604, 5622, and 5624: 150°F (65.6°C)
- Operating Humidity Range 5 to 95% RH non-condensing
- Dimensions with mounting bracket Diameter: 4.57 inches (11.6cm) Height: 1.69 inches (4.3cm)
- Alarm Temperature 5601P, 5603, 5621, and 5623: 135°F (57°C)5602, 5604, 5622, and 5624: 194°F (90°C)
- Weight 6 oz. (170 grams)
- Rate-of-Rise Threshold 15°F (8.3°C) rise per minute (models 5601P, 5602, 5621, and 5622 only)
- Mounting 3½-inch octagonal back box4-inch octagonal back boxSingle gang back box 4-inch square back box with a square to round plaster ring
Electrical Specifications
- Operating Voltage / Contact Ratings 6–125VAC / 3A6–28VDC / 1A125VDC / 0.3A250VDC / 0.1A
- Input Terminals 14–22 AWG