Intelligent monitor modules for NOTIFIER's FireWarden.
Overview
NOTIFIER offers a variety of intelligent monitor modules for diverse applications. Monitor modules supervise a circuit of dry-contact input devices, such as conventional heat detectors and pull stations, or monitor and power a circuit of two-wire smoke detectors (NZM-100).
Features & Benefits:
- Built-in type identification automatically identifies this device as a monitor module to the control panel
- SEMS screws with clamping plates for ease of wiring Direct-dial entry of address: 01 – 99
- LED indication for normal or off normal indication
NMM-100 Monitor Module
- Class A supervised wiring to the monitored device
NMM-100P Mini Monitor Module
- Class B supervised wiring to the monitored device
- Smaller size fits inside devices or junction boxes
NZM-100 Zone Interface Monitor Module
- Transmits the status of one zone of 2-wire detectors to the fire alarm control panel
- Status conditions are reported as normal, open, or alarm
NDM-100 Dual Monitor Module
- Monitors two separate Class B circuits
Specifications
- Temperature Range: 32°F to 120°F (0°C to 49°C)
- Normal Operating Voltage: 15 to 32 VDC
NMM-100:
- Maximum Current Draw: 5.0 mA (LED on)
- EOL Resistance: 47K Ohms
NMM-100P:
- Operating Current: 350 μA max., 1 communication every 5 seconds, 47K EOL resistor; 600 μA max. (Communicating, IDC shorted)
- EOL resistance: 47K Ohms
NZM-100:
- Maximum Current Draw: 5.1 mA (LED on)
- EOL Resistance: 3.9K Ohms
NDM-100:
- Maximum Current Draw: 6.4 mA (LED on)
- EOL Resistance: 47K Ohms
Listings:
- UL: S635
- FM Approved
- CSFM: 7300-0028:0230 (NMM-100, NMM-100P, NZM-100); 7300-0028:0237 (NDM-100)
- MEA: 72-01-E Vol. 2 (NMM-100, NMM-100P, NZM-100); 227-03-E Vol. 3 (NDM-100)