The LEDSIGN-GW Sign Interface monitors events on NOTI-FIRE-NET™ networks and generates appropriate messages on OAX2-24V2 LED displays.
Overview
The OAX2-24V2 LED display is a UL-listed sign which integrates seamlessly with NOTIFIER® fire alarm control panels, NOTI-FIRE-NET™ networks, and ONYXWorks®. In the event of an emergency, the signs will automatically display emergency messages along with optional color changes that demand attention. These messages can be securely controlled from the NOTIFIER® fire alarm control panel (FACP) through encrypted network protocols.
Features & Benefits:
- Controls up to 10 signs with message displays
- Receives zone activations from up to 50 NFN Gateways
- Stores 100 messages per LEDSIGN-GW
- Contains predefined industry standard emergency messages that can be edited
- Transmits custom or default messages according to defined priorities
- Enables a predefined “System Normal” message to be displayed when there are no events
- Overrides system-generated messages upon receipt of manually activated messages from the ONYXWorks® workstation
Specifications
OAX2-24V SPECIFICATIONS:
- LED Colors: Three colors (red, yellow, green)
- LED Size (Diameter): 0.2” (5 mm)
- LED Spacing (Pitch): 0.3” (7.6 mm)
- Character Set: Block profile (sans serif), upper/lower case
- Ethernet: TCP/IP connectivity
- Power: 24V DC, 0.5A
- Mounting: Tilt Wall Mount Bracket, VESA 100mm included
- Weight: 6 lbs
- Dimensions: 7″H x 36″W x 1.75″D
LEDSIGN-GW SPECIFICATIONS:
- The LEDSIGN-GW requires +24VDC @400mA nominal and supervised battery backup in accordance with local code requirements
Listings – LED Sign OAX2-24V2:
- UL 1638
- CSA C22.2 No. 205-M1983
Listings – LEDSIGN-GW:
- UL 864