The SFP-10UD, 10-zone control panel with built-in communicators, provide reliable fire signaling protection for small to medium-sized applications.
Overview
The SFP-10UD, SFP-10UDR (Red backbox), are a UL listed, 10-zone fire alarm control panel with a built-in digital alarm communicator transmitter (DACT) and remote site upload/download capability.
Features & Benefits:
- Ten Class B Initiating Device Circuits (IDCs), Class A optional with N-CAC-5X converter module (2 required)
- Four Class B NACs rated at 3.0 amps, Class A optional with N-CAC-5X converter module (2 required)
- 7.0 amps total system power
- Up to eight ANN-BUS devices (such as LCD annunciators)
- Serial or parallel printer interface
- 80-character LCD display
Specifications
- Initiating Device Circuits: 10 Class B; Class A with optional N-CAC-5X converter module (2 required)
- Notification Appliance Circuits (NACs): 2 Class B; Class A with optional N-CAC-5X converter module each rated for 2.5 amps
- Voice Evacuation Available: Yes, requires direct connect to FireVoice 25/50
- Power: 7.0 amps total system power
- Annunciators: Yes, up to 8 LCD type
- Printer Interface: Yes, serial or parallel
- DACT (Digital Alarm Communicator/Transmitter): Yes
- Built-in Display: 80-character LCD
Listings:
- UL Listed: File S635
- FM Approved
- CSFM: 7165-0028:246
- MEA: MEA: 333-07-E